Case 2. Office Building in Kansas
City, Missouri...

Clients' Concerns: Relatively high magnetic fields in
the first floor offices due to a large transformer vault located directly below.
Many computers were having severe interference problems.
Clients also wished to reduce EMF levels to employees.
Source of the Magnetic Fields: While magnetic fields were
being emitted from several sources in the transformer vault, the largest single
source was from the particular way that the secondary cables were arranged in the ladder trays above
the transformers.
Solution Implemented: The most cost effective mitigation for this
particular case was to simply reconfigure the secondary
cables above the transformers, thus reducing the EMF emissions through
automatic self-cancellation. See the two pictures below...
This
is a picture of the transformer vault before the fix. The offices were
located directly above these transformers. The main source of the EMFs was
from the large electrical cables in the ladder racks above the transformers.
(Please click image for full-sized picture.)
This
is a picture taken after the fix. Some of the large secondary cables above
the transformers have been replaced and rerouted to provide for automatic
self-cancellation. This simple modification was quite effective, yet much
less costly than shielding would have been. (Click image for full-sized picture.)